RETURN

PID temperature controller format 48x48

PID temperature controller format 48×48 N1200 HC

 

Ref . 81202HC120
Temperature controller 48×48 N1020-HC USB Hot/Cold 2 relays


Ref . 81202HC124
Temperature controller 48×48 N1020-HC USB 24V Hot/Cold 2 relays


Ref . 81202HC224
Temperature controller 48×48 N1020-HC USB RS 485 24V Hot/Cold 3 relays


Ref . 81202HC634
Temperature controller 48×48 N1020-HC USB DIO RS 485 Hot/Cold 2 relays


Ref . 81202HC220
Temperature controller 48×48 N1020-HC USB RS 485 Hot/Cold 3 relays


Ref . 81202HC630
Temperature controller 48×48 N1020-HC USB RS 485 Hot/Cold 2 relays

The N1200 process controller is ideal for high-performance control of the most demanding applications. Its advanced, consolidated, self-adaptive PID algorithm guarantees fast, highly accurate response in highly dynamic processes with complex profiles.

The N1200 has the fastest sampling rate of its competitors, resulting in high-speed PID control and ensuring correct process dynamics. Its electronic robustness and flameproof housing material guarantee compliance with the main world-class certifications for industrial devices.

Parameter configuration and fine-tuning can be carried out quickly and easily using the USB port and configuration software.

In addition to the standard configuration of parameters, the N1200 also allows the execution of customized temperature ramp and step profiles, with the programming of up to 20 user recipes or up to 180 segments.

  • Input types:TC J, K, T, N, R, S, B, E, Pt100 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc
  • Accuracy: Thermocouples J, K, T: 0.25% of range ±1 °C; Thermocouples N, R, S, B: 0.25% of range ±3 °C; Pt100, 0-20 mA, 4-20 mA, 0-5 Vdc, 0-10 Vdc: 0.2% of range
  • Input resolution: 32767 levels (15 bits)
  • Sampling rate: 55 samples per second
  • Analog output: 0-20 mA or 4-20 mA
  • Output resolution: 31,000 levels
  •  Control types: PID, PI, PD, P; On/Off
  • Control action: Heating or cooling
  • Control output types: SSR pulse; 4-20 mA control; Relay
  • Open sensor detection: Open loop / Open resistor
  • Alarm types: minimum, maximum, differential, minimum differential, maximum differential, open sensor, ramp and level events
  • Optional: Relay, two digital inputs and outputs, RS485, burnt resistance detection
  • Communication: RS485 Modbus optional
  • Ramps and landings: 20 programs, each with 9 segments
  • Security: parameters protected by access code
  • Configuration interface: USB mini B
  • Power supply: 100-240 Vac/dc; 12-24 Vdc
  • Maximum power consumption: 9 VA
  • Front panel: IP65; Polycarbonate (PC) UL94 V-2
  • Enclosure: IP20; 48 x 48 x 110 mm (DIN 1/16); ABS+PC UL94 V-0
  • Operating conditions: 5 to 50°C and 0 to 80% RH
  • Certification: CE, RoHs, Reach, UL and cUL