The N1500 universal process indicator features a high sampling rate, guaranteeing high-performance indication and rapid response to dynamic processes. With 6 digits for high-resolution variables and a display with 17 mm high digits, the N1500 offers a clear display and easy reading and diagnosis for remote operators.
Its timer function is highly actionable, with alarms for safety interlock logic. What's more, the N1500 is fully compatible with customized input signals, thanks to linearization up to 30 points. Its electronic robustness and flameproof housing material guarantee compliance with the main world-class certifications for industrial devices.
- Display: 7-segment LED, 6 digits, 17 mm high
- Input types: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA non-linear, 0-20 mA custom linear, 4-20 mA custom linear, 0-20 mA custom non-linear, 4-20 mA custom non-linear
- Accuracy: Thermocouples J, K, T: 0.25% of span ±1 °C; Thermocouples N, R, S, B: 0.25% of span ± 3 °C; Pt100, 0-20 mA, 4-20 mA, 0-5 Vdc, 0-10 Vdc: 0.2% of span
- Sampling rate: 5 samples per second for Pt100 and T/C; 15 samples per second for 0-50 mV, 4-20 mA, 0-5 V and 0-10 V
- Display: 7-segment LED, 6 digits, 17 mm high
- Input types: Thermocouples J, K, T, N, R, S, B, E, Pt100, 0-20 mA, 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc, 4-20 mA non-linear, 0-20 mA custom linear, 4-20 mA custom linear, 0-20 mA custom non-linear, 4-20 mA custom non-linear.
- Accuracy: Thermocouples J, K, T: 0.25% of span ±1 °C; Thermocouples N, R, S, B: 0.25% of span ± 3 °C; Pt100, 0-20 mA, 4-20 mA, 0-5 Vdc, 0-10 Vdc: 0.2% of span
- Sampling rate: 5 samples per second for Pt100 and T/C; 15 samples per second for 0-50 mV, 4-20 mA, 0-5 V and 0-10 V
- Display resolution: Temperature: 1 / 0.1; Other measurements: 1 / 0.1 / 0.01 / 0.001 / 0.0001
- Custom linearization: 30 points for non-standard sensors
- Digital input: Key function for Hold, Peak Hold and minimum and maximum zeroing.
- Analog output: 0-20 mA or 4-20 mA (optional) - electrically isolated
- Alarms: Up to 4 alarms
- Alarm types: minimum, maximum, minimum differential, maximum differential, differential out of output range, open sensor.
- Timer: Alarms with timer in delay, pulse or oscillator mode.
- Auxiliary source: 24 Vdc
- Optional: 2 relays, analog output (4-20 mA or 0-20 mA), RS485
- Communication: RS485 Modbus RTU optional
- Mathematical function: Square root
- Security: configuration protected by access code
- Configuration interface: Via RS485
- Power supply: 100-240 Vac/dc or 12-24 Vdc
- Maximum power consumption: 7.5 VA
- Dimensions: 96 x 48 x 92 mm (1/8 DIN)
- Front panel: IP65; Polycarbonate (PC) UL94 V-2
- Enclosure: IP20; Back ABS + PC UL94 V-0
- Operating conditions: 5 to 50°C and 0 to 80% RH up to 30°C
- Certifications: CE, UL and cUL